Sweden Building 05K0013
From Open Energy Information
Start Page
General Information
Year of construction | 1850 |
---|---|
Category | Office |
Boundaries | One building |
Ownership Category | Government building |
Total floor area (BRA), m2 | 19551.0 |
OID, m2 | 20156.0 |
Interior height, m | 3.0 |
Year of construction 1 (taxation year) | 1992 |
Year of construction 2 (Year of construction) | 1850 |
County | Stockholm County, Sweden |
Mean annual temperature during the calculation period[1] | 7.73333333333 |
Mean annual temperature at the site | 6.6 |
Start of the period (first day of the month) | 2004/10/01 |
End of the period (last day of the month) | 2005/09/01 |
References | Swedish Energy Agency[2] |
Areas by category, m2 (Gross Floor Area)
- Restaurants | 215.0 |
---|---|
- Offices | 15632.0 |
- Shops | 154.0
|
- Miscellaneous | 3550.0 |
Total | 19551.0 |
References | Swedish Energy Agency[2] |
Purchased energy for the period [MWh/year]
Electricity, total | 1199.0 |
---|---|
District heating | 1704.0 |
Oil-fired boiler | 0.0 |
Natural gas | 0.0 |
Town gas | 0.0 |
Digester / landfill gas | 0.0 |
Pellets | 0.0 |
Wood chips | 0.0 |
Logs | 0.0 |
District cooling | 420.0 |
Other | 0.0 |
Total | 3323.0 |
References | Swedish Energy Agency[2] |
Purchased energy, normal year [MWh/year]
Electricity, total | 1199.0 |
---|---|
District heating | 1817.6002445 |
Oil-fired boiler | 0.0 |
Natural gas | 0.0 |
Town gas | 0.0 |
Digester / landfill gas | 0.0 |
Pellets | 0.0 |
Wood chips | 0.0 |
Logs | 0.0 |
District cooling | 420.0 |
Other | 0.0 |
Total | 3436.6002445 |
References | Swedish Energy Agency[2] |
Purchased energy per area [kWh/m2]
Electricity, total | 61.3267863536 |
---|---|
Electric heating | 0.0 |
Other electricity | 61.3267863536 |
District heating | 92.9671241624 |
Oil-fired boiler | 0.0 |
Natural gas | 0.0 |
Town gas | 0.0 |
Digester / landfill gas | 0.0 |
Pellets | 0.0 |
Wood chips | 0.0 |
Logs | 0.0 |
District cooling | 21.4822771214 |
Other | 0.0 |
Total | 175.776187637 |
Breakdown of electricity use [kWh/m2]
Electric heating | 0.0 |
---|---|
Heat pumps | 0.0 |
Refrigeration | 0.895094880057 |
Heat pumps used for cooling | 0.0 |
Pumps | 2.63132906976 |
Fans | 16.7539365907 |
Lighting | 21.6361810339 |
PCs | 8.43270214944 |
Large computers / servers | 0.0 |
Printers | 0.549891248721 |
Copiers | 1.24104401228 |
Air compressors | 0.0 |
Small kitchens / coffee rooms | 1.54234902764 |
Large kitchens | 0.0 |
Elevators | 0.163674492353 |
Laundry | 0.0 |
Electric engine heaters | 0.0 |
Circulation fans | 0.767224182906 |
Miscellaneous | 14.2856105095 |
Total | 68.8990371973 |
References | Swedish Energy Agency[2] |
Breakdown of electricity use [%]
Electric heating | 0.0 |
---|---|
Heat pumps | 0.0 |
Refrigeration | 1.29913989581 |
Heat pumps used for cooling | 0.0 |
Pumps | 3.81910862154 |
Fans | 24.3166483485 |
Lighting | 31.4027334982 |
PCs | 12.2392162394 |
Large computers / servers | 0.0 |
Printers | 0.798111658869 |
Copiers | 1.80125015206 |
Air compressors | 0.0 |
Small kitchens / coffee rooms | 2.23856397763 |
Large kitchens | 0.0 |
Elevators | 0.237557009519 |
Laundry | 0.0 |
Electric engine heaters | 0.0 |
Circulation fans | 1.11354848212 |
Miscellaneous | 20.7341221164 |
Total | 100.0 |
References | Swedish Energy Agency[2] |