Sweden Building 05K0017
Building/Boundaries One building  +
Building/Category Office  +
Building/County Stockholm County, Sweden: Energy Resources +
Building/EndPeriod September 1, 2005  +
Building/FloorAreaOffices 18,050  +
Building/FloorAreaShops 3,150  +
Building/FloorAreaTotal 21,200  +
Building/InteriorHeight 3  +
Building/MeanAnnualTempAtSite 6.6  +
Building/MeanAnnualTempCalculationPeriod 7.733  +
Building/Oid 21,860  +
Building/OwnershipCategory Government building  +
Building/SPBreakdownOfElctrcityUseKwhM2AirCompressors 0.820498614958  +
Building/SPBreakdownOfElctrcityUseKwhM2CirculationFans 12.8700390431  +
Building/SPBreakdownOfElctrcityUseKwhM2Copiers 0.0  +
Building/SPBreakdownOfElctrcityUseKwhM2ElctrcEngineHeaters 4.85318559557  +
Building/SPBreakdownOfElctrcityUseKwhM2ElctrcHeating 0.0  +
Building/SPBreakdownOfElctrcityUseKwhM2Elevators 0.0  +
Building/SPBreakdownOfElctrcityUseKwhM2Fans 14.2549696765  +
Building/SPBreakdownOfElctrcityUseKwhM2HeatPumps 0.0  +
Building/SPBreakdownOfElctrcityUseKwhM2HeatPumpsUsedForColg 0.0  +
Building/SPBreakdownOfElctrcityUseKwhM2LargeComputersServers 0.397396121884  +
Building/SPBreakdownOfElctrcityUseKwhM2LargeKitchens 0.16620498615  +
Building/SPBreakdownOfElctrcityUseKwhM2Laundry 0.0  +
Building/SPBreakdownOfElctrcityUseKwhM2Lighting 17.1625971143  +
Building/SPBreakdownOfElctrcityUseKwhM2Misc 0.0  +
Building/SPBreakdownOfElctrcityUseKwhM2Pcs 24.4079778393  +
Building/SPBreakdownOfElctrcityUseKwhM2Printers 0.673130193906  +
Building/SPBreakdownOfElctrcityUseKwhM2Pumps 4.15013278976  +
Building/SPBreakdownOfElctrcityUseKwhM2Refrigeration 0.0  +
Building/SPBreakdownOfElctrcityUseKwhM2SmallKitchensCoffeeRms 0.0  +
Building/SPBreakdownOfElctrcityUseKwhM2Total 79.7561319756  +
Building/SPElectrtyUsePercAirCompressors 1.02875928739  +
Building/SPElectrtyUsePercCirculationFans 16.1367392379  +
Building/SPElectrtyUsePercCopiers 0.0  +
Building/SPElectrtyUsePercElctrcEngineHeaters 6.08503130149  +
Building/SPElectrtyUsePercElctrcHeating 0.0  +
Building/SPElectrtyUsePercElevators 0.0  +
Building/SPElectrtyUsePercFans 17.8731958577  +
Building/SPElectrtyUsePercHeatPumps 0.0  +
Building/SPElectrtyUsePercHeatPumpsUsedForColg 0.0  +
Building/SPElectrtyUsePercLargeComputersServers 0.49826403568  +
Building/SPElectrtyUsePercLargeKitchens 0.208391482928  +
Building/SPElectrtyUsePercLaundry 0.0  +
Building/SPElectrtyUsePercLighting 21.5188433656  +
Building/SPElectrtyUsePercMisc 0.0  +
Building/SPElectrtyUsePercPcs 30.6032617615  +
Building/SPElectrtyUsePercPrinters 0.843985505857  +
Building/SPElectrtyUsePercPumps 5.20352816387  +
Building/SPElectrtyUsePercRefrigeration 0.0  +
Building/SPElectrtyUsePercSmallKitchensCoffeeRms 0.0  +
Building/SPElectrtyUsePercTotal 100.0  +
Building/SPPurchasedEngyForPeriodMwhYrDigesterLandfillGas 0.0  +
Building/SPPurchasedEngyForPeriodMwhYrDstrtColg 850.0  +
Building/SPPurchasedEngyForPeriodMwhYrDstrtHeating 1460.0  +
Building/SPPurchasedEngyForPeriodMwhYrElctrtyTotal 1450.0  +
Building/SPPurchasedEngyForPeriodMwhYrLogs 0.0  +
Building/SPPurchasedEngyForPeriodMwhYrNaturalGas 0.0  +
Building/SPPurchasedEngyForPeriodMwhYrOil-FiredBoiler 0.0  +
Building/SPPurchasedEngyForPeriodMwhYrOther 0.0  +
Building/SPPurchasedEngyForPeriodMwhYrPellets 0.0  +
Building/SPPurchasedEngyForPeriodMwhYrTotal 3760.0  +
Building/SPPurchasedEngyForPeriodMwhYrTownGas 0.0  +
Building/SPPurchasedEngyForPeriodMwhYrWoodChips 0.0  +
Building/SPPurchasedEngyNrmlYrMwhYrDigesterLandfillGas 0.0  +
Building/SPPurchasedEngyNrmlYrMwhYrDstrtColg 850.0  +
Building/SPPurchasedEngyNrmlYrMwhYrDstrtHeating 1551.0  +
Building/SPPurchasedEngyNrmlYrMwhYrElctrtyTotal 1450.0  +
Building/SPPurchasedEngyNrmlYrMwhYrLogs 0.0  +
Building/SPPurchasedEngyNrmlYrMwhYrNaturalGas 0.0  +
Building/SPPurchasedEngyNrmlYrMwhYrOil-FiredBoiler 0.0  +
Building/SPPurchasedEngyNrmlYrMwhYrOther 0.0  +
Building/SPPurchasedEngyNrmlYrMwhYrPellets 0.0  +
Building/SPPurchasedEngyNrmlYrMwhYrTotal 3851.0  +
Building/SPPurchasedEngyNrmlYrMwhYrTownGas 0.0  +
Building/SPPurchasedEngyNrmlYrMwhYrWoodChips 0.0  +
Building/SPPurchasedEngyPerAreaKwhM2DigesterLandfillGas 0.0  +
Building/SPPurchasedEngyPerAreaKwhM2DstrtColg 40.0943396226  +
Building/SPPurchasedEngyPerAreaKwhM2DstrtHeating 73.1603773585  +
Building/SPPurchasedEngyPerAreaKwhM2ElctrcHeating 0.0  +
Building/SPPurchasedEngyPerAreaKwhM2ElctrtyTotal 68.3962264151  +
Building/SPPurchasedEngyPerAreaKwhM2Logs 0.0  +
Building/SPPurchasedEngyPerAreaKwhM2NaturalGas 0.0  +
Building/SPPurchasedEngyPerAreaKwhM2Oil-FiredBoiler 0.0  +
Building/SPPurchasedEngyPerAreaKwhM2Other 0.0  +
Building/SPPurchasedEngyPerAreaKwhM2OtherElctrty 68.3962264151  +
Building/SPPurchasedEngyPerAreaKwhM2Pellets 0.0  +
Building/SPPurchasedEngyPerAreaKwhM2Total 181.650943396  +
Building/SPPurchasedEngyPerAreaKwhM2TownGas 0.0  +
Building/SPPurchasedEngyPerAreaKwhM2WoodChips 0.0  +
Building/StartPeriod October 1, 2004  +
Building/TotalFloorArea 21,200  +
Building/YearConstruction 1987  +
Building/YearConstruction1 1987  +
Building/YearConstruction2 1987  +
Categories Sweden Buildings